microFLEX M2B Controller
Single Boiler/Condensate Controller
The ProMinent® microFLEX is a powerful controller integrating built-in diagnostics with realtime monitoring in a compact design.
Request more info
Standard Features
- Boiler or Condensate Conductivity input
- Single water meter input
- Boiler status input
- Chemical feed relay
- 5 Key universal keypad
- 2 Line, 16 character backlit display
- Boiler blowdown or condensate diverter relay (solenoid valve or motorized ball valve)
Benefits
- Selectable chemical feed mode: Provides 3 feed modes; feed on volume, blowdown & feed and percentage time.
- Conductivity control: Can be programmed using timed or continuous sampling.
- Water meter input: Allows for chemical to be fed based on water volume versus timed pump control methods generally found on comparably priced controllers.
- What and Why Information: Diagnostics shown on display are a valuable troubleshooting tool. Conductivity valve and chemical pump relays show complete stauts. Shows WHY the relay is on/off.
- Single point calibration: For ease of start up and operation. Warning message immediately detects foulled or faulty sensors.
- Controller run time: Gives total hours per day and total operating days since initial installation.
- Robust diagnostics: Provides complete 24 hour history of blowdown valve operation and chemical relay timing intervals.
- Keypad password: Eliminates unauthorized adjustments.
- Communication options: Includes Ethernet networking, dry contact alarm relay or 4-20mA output on conductivity.
- Optional web browser user interface with networking capability: Provides ability to direct connect to the controller from a portable workstation, such as a laptop computer. Can also view critical processes remotely through the use of a LAN.
Image Download
Note: Click on image to download
Rating - Detail | Notes | |
---|---|---|
Analog-Digital I/O | ||
Conductivity Sensor | Auto ranging from 100uS to 10,000uS, rated 250psi | Single point calibration |
Water Meter Input current | 400Hz, 0.5mA @ 5VDC measurement head | Accepts paddlewheel or contacting |
Relay Outputs 1 SPDT (Bleed) | 1 SPST (Chemical feed), valve | Powers either solenoid or motorized |
4-20mA Output (optional) | Single DC isolated, loop powered loop | User definable span, alarms on open |
Alarm Relay (optional) | 500mA @ 24VDC Dry contact set, unfused | Normally closed contact, open on alarm |
Communications User Interface | ||
Keypad-LCD | 5 Key tactile feedback, universal characters, 2 line x 16 character, backlit | Scan rate 100 mS nominal, User adjustale contrast |
10 Base T, TCP/IP Ethernet LAN (optional) | HTML micro web server with user definable IP address | Static IP, Use browser to see I/O, edit program |
Controls | ||
Relay ON/OFF | Captured sample & ON/OFF control valve | Relay 1 chemical feed, Relay 2 bleed |
Volumetric feed | User set, measure volume & pump on time | |
Interlocking | Contact set input | Blowdown & feed stop |
Alarms - Feed Limit Timers | Minutes per day | Auto-reset @ Midnight |
System | ||
Electrical | 120VAC, 60Hz | |
Fusing | 5 AMPS @ 120VAC | |
Surge Suppression | Relay 2 N.O. contacts snubbed @ 0.1uF, 150ohm | Varistor on AC line input |
Accessory Power fused @ 50mA | 15-22VDC, unregulated, thermally | |
Enclosure | Non-metallic, NEMA 4X | 5.9”W x 5.9”H x 3.5”D (150mmW x 150mmH x 90mmD) |
Certifications | ||
CSA, CE, UL | CSA tested to comply with UL |