multiFLEX M5T/M10T Controller


Cooling Tower Controller

The ProMinent® multiFLEX is a completely customizable microprocessor that provides the highest degree of control and flexibility.  Unlock the full potential of your program using Plug and Play Technology and Trackster 3 software.


Request more info


Standard Features

  • Control multiple cooling towers
  • Web browser accessible
  • LAN accessible
  • Up to 14 analog inputs or outputs
  • Up to 12 digital inputs
  • Up o 10 relay outputs
  • Compatible with Trackster 3 software

Benefits

  • Flexible Control: Multiple processes can be managed using any number of combinations with one controller.
  • Data Logging: Detailed data history provides sensor minimum, maximum and average per each log period. Also records pump run times, pump feed volume, calculated drum levels, water meter volume and tower run time.
  • Exclusive Thermal Flow Switch: Innovative design does not require user adjustment or calibration. Operates on 1GPM flow rate with no moving parts.
  • Feed Verification: HIghly accurate chemical feed with 1mL resolution. Calculates, displays and data logs chemical ppm based on system parameters. Alarms on failure to feed. Additional feature provides tank inventory and low tank level alarm without the use of level sensors.
  • Communications: TModem, Ethernet TCP/IP and keypad programmable. Remotely monitor and control your water treatment program on any computer and from anywhere in the world with the use of a standard web browser.
  • Plug and Play Onsite Upgrades: The multiFLEX features Plug and Play technology allowing the user to perform simple and economical onsite upgrades.
  • multiFLEX Advanced Technology: Maximize your treatment potential with ProMinent’s exclusive features. Rate to Volume, Rate to Stroke, Timed Cycling and Time Modulation provide progressive control, taking your program to a whole new level!
  • Drum Level Management: Provide digital low level indication or utilize our analog tank sensor to view level in gallons, inches or liters.
  • Trackster Software: Trackster 3 Software completes the package, providing the ultimate in program management. Features such as customized live views, alarm notification, graphing and reporting of all I/O data with exporting capabilities, and email of historical data are all possible with the use of this powerful tool.

 

Rating - Detail Notes
M5T M10T M5T M10T
Analog-Digital I/O
Analog Inputs and Outputs 1-7 inputs for sensors, 4-20mA inputs / 4-20mA outputs 1-14 inputs for sensors, 4-20mA inputs / 4-20mA outputs Auto configuration on driver installation & removal, DC Isolated, Loop Powered
Digital Inputs 6 Inputs 12 Inputs User configurable as water meters or contact sets
Relay Outputs 1SPST, 4 SPDT 2 SPST, 8 SPDT Fused in sets of 5 relays
Alarm Relay (optional) Dry Contact set, un-fused User selected NO or NC
Communications User Interface
Keypad-LCD 5 Key tactile feedback, Universal Characters, 4 line x 20 Character, Backlit Scan rate 100 mS nominal, User adjustale contrast
10 Base T, TCP/IP Ethernet LAN HTML, Telnet Micro Web Server, User Definable IP address & port Password, User ID protected, Browser shows controller in real time
Modem (optional) 56K, V.90 Remote Telnet Access Dial-out on alarms to pager or PC
Data Logging 600 Entries for each, 26 inputs & 5 relays, Stored in XML format 600 Entries for each, 26 inputs & 10 relays, Stored in XML format Adjustable from 5 to 1440 minutes per entry
Controls
Relay ON/OFF ON/OFF control Any relay can be configured for any control
Proportional 4-20mA (optional) User defined control set by sensor or relay control Software ZERO & SPAN adjustments
Volumetric User set, measure volume & pump on time then bleeds for user set volume Sequential control, measures make-up volume
Captured Sample Sample, Measure, Blowdown, Resample user set timing Any sensor may be used
Interlocking 1 to 4 contact set inputs, AND & OR support Relays OFF when contact set opens
Blocking 1 to 4 relays may block any other relay feed Support for common Oxidant-Inhibitor
Alarms - Feed Limit Timers Minutes per Actuation & Day User defined on Feed Limit
Feed Verfication (optional) PPM calculation based on volume feed & cycles of concentration Fail to Feed is no volume counted after 30 seconds of pump ON time
System
Electrical 120/240VAC, 50/60Hz Switch Selectable
Fusing 7.3 Amps @ 120VAC, 4.15 Amps @240VAC Relay Fused 1-5 & 6-10, 6.3A ea. Logic fused @ 1A
Surge Suppression Relays 2-5 & 7-10 NO Contacts snubbed @ 0.1uF Controller Isolated from AC line
Accessory Power 15-22VDC, Unregulated, thermally fused @ 200mA
Enclosure Non-metallic, NEMA 4X, IP65 11.5”W x 13.5”H x 7”D
Certifications
CSA, CE, UL CSA tested to comply with UL